CDWN/CDDN&CDWC Carbon Dioxide (CO2) Transmitter/Controller
Applications & Features
- CD-N series carbon dioxide transmitters/controllers are designed for monitoring & controlling indoor air quality
- CDWN/CDWC is suitable for wall mount and CDDN is suitable for duct mount
- High performance NDIR digital sensor and circuit, ensure precise measurement and temperature compensation
- Stable, reliable and fast response
- 15 years sensor life without maintenance
- Digital technology applied, over voltage and reverse polarity protection, high reliability and anti-interference capability
- All electrical terminals are on the inside bottom, avoid any possible destroy to PCB when wiring (for CDWN/CDWC)
- Multiple outputs selection
- LCD & function keys can set various parameters, calibrate and adjust output, so the product can be a stand-alone controller (for CDWC)
Specifications for CDWN (wall mount) &CDDN (Duct)
- Sensor: NDIR sensor, with ABC algorithm
- Sampling Method: diffusion
- Accuracy: see models
- Response time: <120s (30cc/min, low airflow)
- Drift: <±10ppm/year
- Range: 0~2000ppm (Measurement range 400~2000 ppm)
- Output: 4~20mA, 0~10V, RS485/Modbus
- Load resistance: ≤500Ω (Current output),
≥2kΩ (Voltage output)
- Power supply: 16~28VAC/16~35VDC
- Display: Optional LCD (CDWN), with unit display
- Display resolution: 1ppm
- Working environment: 0~50°C , 0~85%RH (Non-cond.)
- Temp. Compensation: CDWN0/CDDN0:10~40°C
CDWN1/CDDN1:0~50°C
- Storage temperature: -20~60°C
- Housing: ABS+PC (CDWN), fireproof ABS (CDDN)
- Protection: IP30 (CDWN), IP65 (CDDN)
- Weight: 135g (CDWN), 230g (CDDN)
- Approval: CE
- ABC algorithm:
Automatic Baseline Correction, it constantly keeps track of the sensor's lowest reading over a few days interval and slowly corrects for any long term drift detected as compared to the expected fresh air value of 400 ppm CO2.
Models for CDWN&CDDN
Model | CDWN |
|
| Wall mount CO2 Transmitter Duct mount CO2 Transmitter |
Accuracy | CDDN |
|
| 50 ppm + 5% reading 40 ppm + 3% reading |
Output |
| 0 |
| 4~20mA & 0~10VDC 4~20mA & 0~10VDC RS485/Modbus |
1 | ||||
Display (CDWN |
|
| 0 | N/A LCD |
1 |
Specifications for CDWC
- Sensor: NDIR sensor, with ABC algorithm
- Sampling Method: diffusion
- Accuracy: see models Temp.
- Compensation: CDWC0:10~40°C; CDWC1:0~50°C
- Response time: <120s (30cc/min, low airflow)
- Drift: <±10ppm/year
- Range: 0~2000 ppm (measure range 400~2000ppm)
- Output: 2×SPST, 3A-30VDC/250VAC
- Communication: optional RS485/Modbus
- Power supply: 16~28VAC/16-35VDC
- Display and keys: with LCD Display and 3 touch keys, see more details on LCD & Keys operation Display resolution: 1ppm
- Working environment: 0~50°C , 0~85%RH (Non-cond.)
- Storage temperature: -20~60°C
- Housing: ABS+PC
- Protection: IP30
- Weight: 135g
Approval: CE Models for CDWC
Model | CDWC |
|
| Wall mount CO2 Controller |
Accuracy |
| 0 |
| 50 ppm + 5% reading 40 ppm + 3% reading |
1 | ||||
Communication |
|
| 0 | N/A RS485/Modbus |
1 |